Evaluation of Evacuation Mapping in Industrial Fire Scenarios using CFD tools
DOI:
https://doi.org/10.38032/scse.2026.4.11Keywords:
ASET, RSET, Carbon Monoxide, Soot Density, CFD Tool, NISTAbstract
Recently Bangladesh has witnessed a significant rise in industrial fire incidents. These structures often lack adequate fire safety systems causing smoke propagation during emergencies. This study evaluates the design of an industrial building comprising of 2 floors with an opening between them using Computational Fluid Dynamics (CFD) tool. The structure was simulated using PyroSim with two varying fire location. The environment was simulated for 12 minutes since ignition with a medium fire size. It was seen, within 3 minutes, smoke can engulf all exits of the storage room reducing visibility to dangerous level if fire source is in fabric storage. Comparative analyses show if fire is originated in production area, smoke migration is delayed offering better evacuation opportunities in ground floor. Toxic combustion product of cellulosic fuels like carbon monoxide (CO) cause intoxication and loss of consciousness whereas soot reduces the visibility. It is therefore important to predict the smoke conditions in a building during fire and find the ratio of ASET (Available Safety Egress Time) & RSET (Required Safety Egress Time). This study highlights importance of performance-based fire safety design, where perspective-based design falls short.
Downloads
Downloads
Downloads
References
[1] McGrattan, K., Hostikka, S., Floyd, J., Baum, H., Rehm, R., Mell, W. and McDermott, R. (2010) Fire Dynamics Simulator (Version 5): Technical Reference Guide – Volume 1: Mathematical Model. NIST Special Publication 1018-5. Gaithersburg, MD: National Institute of Standards and Technology.
[2] Smardz, P. (2006) Validation of Fire Dynamics Simulator (FDS) for forced and natural convection flows. MSc thesis. Department of Fire Safety Engineering, University of Ulster.
[3] Leonard, A. (1974) ‘Energy cascade in large-eddy simulations of turbulent fluid flows’, Advances in Geophysics, 18, pp. 237–248. DOI: https://doi.org/10.1016/S0065-2687(08)60464-1
[4] McGrattan, K., Hostikka, S., Floyd, J., Baum, H., Rehm, R., Mell, W. and McDermott, R. (2010) Fire Dynamics Simulator (Version 5): Technical Reference Guide – Volume 1: Mathematical Model. NIST Special Publication 1018-5. Gaithersburg, MD: National Institute of Standards and Technology.
[5] Hurley, M.J. (ed.) (2016) SFPE Handbook of Fire Protection Engineering. 5th edn. Cham, Switzerland: Springer.
[6] National Institute of Standards and Technology (n.d.) NIST Special Publication 1018. Gaithersburg, MD: National Institute of Standards and Technology.
[7] McGrattan, K. (2006) Fire Dynamics Simulator (Version 4): Technical Reference Guide. NIST Special Publication 1018. Gaithersburg, MD: National Institute of Standards and Technology. DOI: https://doi.org/10.6028/NIST.SP.1018
[8] Kashef, A., Bénichou, N., Lougheed, G. and Debs, A. (n.d.) ‘Prediction of smoke propagation in a big multi-story building using Fire Dynamics Simulator (FDS)’, American Journal of Energy Engineering. Science Publishing Group.
[9] Kallianiotis, A., Papakonstantinou, D., Tolias, I.C. and Benardos, A. (2021) ‘Evaluation of fire smoke control in underground space’, Underground Space, 7(2), pp. 295–310. DOI: https://doi.org/10.1016/j.undsp.2021.07.010
Published
Conference Proceedings Volume
Section
License
Copyright (c) 2026 Md. Kharshiduzzaman, Musfiqul Azad , Syed Ishfaqul Hoque Rafsan, Mafrur Faharrim Khan , Redwanur Rashid , Md Foysal Mahmud (Author)

This work is licensed under a Creative Commons Attribution 4.0 International License.
All the articles published by this journal are licensed under a Creative Commons Attribution 4.0 International License